dv/dt Filter FN5060HVdv/dt Filter FN5060HV

dv/dt Filters dv/dt Filter FN5060HV

Output Filter for Motor Drives

dv/dt Filter FN5060HV

Output Filter for Motor Drives

  • Reduction of drive output voltage dv/dt
  • Reduction of voltage stress at motor windings
  • Protect AC motors from destructive effect of peak voltages
  • Increase of motor service life
  • Improvement of system reliability

Features and Benefits

Efficient reduction of high output voltage dv/dt from IGBT motor drives (as per IEC 60034-17/25)
Restriction of overvoltages caused by line reflections on motor cables (as per IEC 60034-17/25)
Protection of motor winding insulation from premature aging and destruction
Increase service life of electric motors
Patented solution without capacitors and resistors for ease of installation and increased reliability
Less interference propagation towards neighbouring equipment or lines
Output filter with low impedance, ideal for processes requiring exceptional precision and reproducibility of movements

Typical Applications

Motor drive applications with short to medium motor cable length
Machinery comprising servo or torque motors
Submersible- and irrigation pumps
HVAC equipment, incl. pumps, fans and compressors
Elevators, hoisting and cranes
Motor drives for process lines
Applications where sine wave filters are not suited (e.g. high dynamic operation)

Technical Specifications

Max. operating voltage

3 ph 760 VAC

Flammability corresponding to

UL 94V-2

Max. peak voltage

≤1850 V (according EN 60034-25B)

Voltage drop

<3 V @ 50 Hz

Rated temperature

+40°C without derating up to 100°C

Operation temperature

-25°C to +100°C (25/100/21)

Overload capability

1.5 x rated current for 1 minute, once per hour

Protection category

IP 00

Design corresponding to

UL 61800-5-1, CSA 22.2 No.14, EN 61558-2-20

Rated currents

30 to 1200 A

Rated currents

30 to 1200 A @ 40°C

Transportation and storage temperature

-40°C to +100°C (25/100/21)

Motor frequency

0 to 60 Hz

0...60 Hz (with derating up to 120 Hz)

Motor frequency

0...60 Hz (with derating up to 120 Hz)

Switching frequency

up to 16 kHz, depending on motor cable lenght and motor frequency -> refer graph on page 2

Switching frequency

0 to 16 kHz

up to 16 kHz, depending on motor cable lenght and motor frequency -> refer graph on page 2

Typical dv/dt reduction

Factor 8 to 12

Typical electrical schematic

dv/dt Filter FN5060HV

Approvals & Compliances

RoHS Label
UL Recognized Label (USA)
CE Label
UKCA Label

UL recognized up to 320 A

Back