Legacy Products Sine Wave Filter FN5040/FN5045

LC Sine Wave Filter for Motor Drives

Sine Wave Filter FN5040/FN5045

LC Sine Wave Filter for Motor Drives

  • Smooth sine wave without voltage peaks
  • Perfect motor protection
  • Reduce bearing currents
  • Motor frequency up to 200 Hz
  • Extended motor cable length capability

Features and Benefits

Converts the rectangular PWM output voltage of motor drives into a smooth sine wave with low residual ripple
Elimination of premature motor damage caused by high dv/dt, overvoltages, cable ringing, motor overheating, and eddy current losses
Improves bearing life time because of bearing currents caused by circulating currents
Complies with IEC 60034-17* and NEMA-MG1 requirements for general purpose motors
Optional with NEMA 1 protective cover

Typical Applications

HVAC applications
Pumps
Ventilators
Conveyors
Compressors
Elevators
Cranes
Medium voltage applications, deployed in front of the step-up transformer
Retrofit installations with motor drives
Motor drive with long motor cable
Motor drive with multiple motors in parallel

Technical Specifications

Nominal operating voltage

3x480 VAC

Motor frequency

0 to 70 Hz

0...70 Hz (up to 200Hz with derating (see graph))

Typical dv/dt reduction

≥factor 5

Rated operating voltage

3x525 VAC

Impedance (uk)

8 to 10% @ 400 V, 50 Hz and rated current

Residual ripple voltage

<5%

High potential test voltage

P –> E 3000 VAC, 1 minute

P –> P 2500 VAC, 1 minute

Protection category

IP 00 (FN 5040)

IP 20 (FN 5045)

Overload capability

1.5× rated current for 1 minute, once per hour

Ambient temperature range

-25°C to +45°C fully operation

+45°C to 70°C derated operation*

-25°C to +85°C transport and storage

Insulation class

EIS 200

Flammability corresponding to

UL 94 V-2

Design corresponding to

Filter: UL 61800-5-1, EN 61800-5-1

Chokes: EN 61558-2-20 or EN 60076-6

Filter: UL 61800-5-1, EN 61800-5-1

Filter: UL 61800-5-1, EN 61800-5-1

Filter: UL 61800-5-1, EN 61800-5-1

MTBF

>100,000 hours

Rated currents

4.5 to 1200 A @50°C (480 V filters)

Switching frequency

2 to 12 kHz

See filter selection table

Rated currents

4.5 to 1200 A @ 45°C

Motor cable length

Up to 2,000 m (see graph)

* Iderated = Inominal*SQRT((Tmax-Tamb)/(Tmax-Tnominal)) = Inominal*SQRT((70°C-Tamb)/25°C)

Typical electrical schematic

Sine Wave Filter FN5040/FN5045

Approvals & Compliances

UL Recognized Label (USA)
RoHS Label
CE Label
UKCA Label

UL 61800-5-1 up to 750 A for FN 5040, 480 A for FN 5045. For use with AC or DC drives (power conversion equipment) only